Measure and transmit data from up to 12 resistance temperature detectors (RTDs) and a single contact status located in transformers, breakers, motors, generators, or other system apparatus.
Applications
Temperature Measurement—Acquire and transmit RTD thermal data from transformers, motors, generators, and other system apparatus.
Compatible With Multiple RTD Types—Connect any one of four different RTD types on each independent input:
100 ohm platinum
100 ohm nickel
120 ohm nickel
10 ohm copper
Wiring Reduction With Optical Interface—Replace expensive RTD cable pulls using a single fiber-optic cable. Measure up to 12 RTD temperatures plus one contact input in one SEL-2600 RTD Module, and send the data back to a compatible device over one fiber-optic cable.
Simple Measurement Integration—Measure and transmit data from RTDs located in transformers, breakers, motors, generators, or other system apparatus in combination with SEL communications processors.
Rugged Design—Operate the SEL-2600 Module in extreme ambient temperatures from –40° to +85°C. The SEL-2600 is conformally coated and rated at Pollution Degree 3 (PD3); UL/CSA/CE recognized; Class I, Zone 2 approved; and corrosion-tested to ASTM B117-03 for salt spray and fog.
Overview
RTD electrical noise rejection up to 1.4 V peak ac = 50 Hz.
Measures up to 12 RTD temperatures plus one contact input.
Allows flexible panel-mounting for locating near RTDs.
Fiber link provides electrical noise immunity and ground isolation between devices.
Accepts 120/240 Vac or 120 Vdc input power.
Illuminates LEDs to indicate contact input status, data transmission, and product enable status.
Operates in extreme ambient temperatures from –40° to +85°C.
Printed circuit boards are conformal-coated to provide an additional barrier to airborne contaminants, such as hydrogen sulfide, chlorine, salt, and moisture.